RS485 Control Dosierung der industriellen Online -PH -ORP -Messgerät
Holen Sie sich aktuelle PreisZahlungsart: | T/T |
Incoterm: | FOB,CIF,EXW,DDP |
Minimum der Bestellmenge: | 1 Piece/Pieces |
Transport: | Ocean,Air,Express |
Hafen: | Shanghai,Guangzhou |
Zahlungsart: | T/T |
Incoterm: | FOB,CIF,EXW,DDP |
Minimum der Bestellmenge: | 1 Piece/Pieces |
Transport: | Ocean,Air,Express |
Hafen: | Shanghai,Guangzhou |
Modell: APX1-C2
Marke: Daruifuno
Support Customization: Oem
Place Of Origin: China
Warranty Period: 1 Year
Certification: CE, ISO9001
Temp. Compensation: Automatic or manual
Resolution: 0.01pH, 1mV, 0.1℃
Display Screen: 3.2 inch LCD
Relay Control: Two SPST relays
Measuring Range: 0~14pH, -2000~2000mV
Protection Grade: IP66
System Language: English
Current Output: Two 0/4-20mA
Verkaufseinheiten | : | Piece/Pieces |
Pakettyp | : | Kartons und Schaum |
Bildbeispiel | : | |
Herunterladen | : |
Daruifuno Online PH Controller APX1-C2 ist ein Instrument, das die reichhaltigen Bedürfnisse der Benutzer erfüllen kann. Es kann mit einer Vielzahl von analogen pH -Sensoren oder ORP -Sensoren verbunden werden, um die kontinuierliche Online -Überwachung der pH- oder ORP -Werte der Wasserqualität zu realisieren. Es verfügt über zwei Relais, die die Kontrolle des pH- oder orp -Werts, der Temperatur und der Reinigung realisieren können. Der Ausgang dieses pH-ORP-Analysators ist auch sehr reich, sondern nicht nur 2 Kanäle mit 4-20 mA-Ausgabe, sondern kann einen pH-Wert oder den ORP-Wert und den Temperaturwert ausgeben, sondern auch die RS485-Schnittstelle unterstützt das Modbus-Kommunikationsprotokoll. Benutzer können den Controller mit verschiedenen SPS anschließen.
Spezifikation
Measurements | pH, ORP |
Measuring Range | pH: 0~14pH ORP: -2000~2000mV Temp.: -10~150℃ |
Resolution | pH: 0.01pH ORP: 1mV Temp.: 0.1℃ |
Temp. Compensation | automatic (PT1000/NTC10K) or manual |
Accuracy | 0.1% of the measuring range or pH: ± 0.02pH, ORP: ±2mV, take the larger one |
Stability | 0.05% of the measurement range every 24 hours, no accumulation |
Repeatability | 0.1% better than measuring range |
Display Screen | 3.2 inch LCD screen |
System Language | English |
Calibration Method | pH: 3 points; ORP: 2 ponits, the calibration points can be set |
Power Failure Protection | The setting data is permanently retained, when the meter is powered off. |
Password | Six-digit passcode setting |
Quick Calibration | A quick calibration menu is available without going to the main menu |
Relay Output |
2 configurable SPST relays,max. load 3A/250VA Csetting objects: high/low alarm, temperature or wash control |
Current Output | Two 0/4~20mA can be set with an active current loop, load 1000Ω, and support long-term calibration |
Digital Output | A two-wire RS485 interface, support Modbus protocol |
Protection Grade | IP66 |
Working Temperature | 0~60°C, relative humidity less than 95%RH (no condensation) |
Storage Temperature | -20~70°C, relative humidity less than 95%RH (no condensation) |
Dimension | 100*100*120mm |
Material | enhanced ABS |
Installation Method | panel installation, hole size:92*92mm |
Electrical Interface | 3 M12*1.5 gland heads, wire diameter 3~6.5mm |
Power Supply | AC:100~240VAC, 50~60Hz;DC:+18~36VDC |
Power Consumption | 3W |
Funktionen